保护等级 | IP20 |
---|---|
环境温度(运行) | -40 °C ... 80 °C |
环境温度(存放/运输) | -40 °C ... 80 °C |
海拔 | ≤ 2000 m (平均海拔(标准海拔零点以上)) |
允许湿度(运行) | 5 % ... 95 % |
冲击力(运行) | 30g (半正弦 / 11 ms/ 3x ±X,±Y, ±Z) |
振动(操作) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
额定电压UN | 240/415 V AC (TN-S) |
---|---|
240/415 V AC (TT) | |
额定频率fN | 50 Hz (60 Hz) |
持续工作电压UC (L-N) | 350 V AC |
持续工作电压UC (L-PE) | 350 V AC |
持续工作电压UC (N-PE) | 264 V AC |
额定负载电流IL | 40 A (Biconnect M4叉形电缆插针6 mm²) |
63 A (TWIN冷压头2 x 10 mm²) | |
残流IPE | ≤ 1 µA |
标称放电电流In (8/20) µs (L-N) | 20 kA |
标称放电电流In (8/20) µs (N-PE) | 20 kA |
放电电流 Imax (8/20) µs (L-N) | 40 kA |
放电电流 Imax (8/20) µs (N-PE) | 40 kA |
额定断开续流值 Ifi (N-PE) | 100 A (264 V AC) |
额定短路电流ISCCR | 25 kA |
电压保护水平Up (L-N) | ≤ 1.5 kV |
电压保护水平Up (L-PE) | ≤ 1.9 kV |
电压保护水平Up (N-PE) | ≤ 1.5 kV |
残压Ures (L-N) | ≤ 1.5 kV (In时) |
≤ 1.3 kV (10 kA时) | |
≤ 1.2 kV (5 kA时) | |
≤ 1.1 kV (4 kA时) | |
≤ 1 kV (2 kA) | |
残压Ures (N-PE) | ≤ 0.5 kV (In时) |
≤ 0.5 kV (10 kA时) | |
≤ 0.5 kV (5 kA时) | |
≤ 0.5 kV (4 kA时) | |
≤ 0.5 kV (2 kA) | |
UT下的TOV动作(L-N) | 415 V AC (5 秒 / 耐受模式) |
440 V AC (120 分钟 / 安全失效模式) | |
UT下的TOV动作(N-PE) | 1200 V AC (200 ms / 耐受模式) |
响应时间tA(L-N) | ≤ 25 ns |
响应时间tA(N-PE) | ≤ 100 ns |
备用保险丝,带有V型连接线 | 40 A (gG / Biconnect M4叉形电缆插针,6 mm²) |
63 A (gG / TWIN冷压头2x 10mm²) | |
备用保险丝,带有支线接线 | 315 A (gG) |