产品简介
倍加福安全栅现货特价销售KFD2-UT2-EX1
倍加福安全栅现货特价销售KFD2-UT2-EX1
产品价格:¥1
上架日期:2012-06-05 15:39:02
产地:德国
发货地:上海
供应数量:不限
最少起订:1块
浏览量:577
资料下载:暂无资料下载
其他下载:暂无相关下载
详细说明
    Release date 2012-04-19 13:49 Date of issue 2012-04-19 132960_eng.xml
    KFD2-SR2-Ex2.W
    Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
    Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 1
    Switch Amplifier
    2+
    3-
    1+
    Zone 2
    Div. 2
    Zone 0, 1, 2
    Div. 1, 2
    KFD2-SR2-Ex2.W
    789
    10
    11
    12
    I
    II
    I
    II
    14+ 24 V DC
    15-
    Power Rail
    ERR 24 V DC
    5+
    6-
    4+
    10 kΩ
    10 kΩ
    400 Ω ≤ R ≤ 2 kΩ
    10 kΩ
    10 kΩ
    400 Ω ≤ R ≤ 2 kΩ
    Connection
    Assembly
    • 2-channel isolated barrier
    • 24 V DC supply (Power Rail)
    • Dry contact or NAMUR bs
    • Relay contact output
    • Line fault detection (LFD)
    • Reversible mode of operation
    • Up to SIL2 acc. to IEC 61508
    Function
    This isolated barrier is used for intrinsic safety applications. It
    transfers digital signals (NAMUR sensors/mechanical
    contacts) from a hazardous area to a safe area.
    The proximity sensor or switch controls a b C changeover
    relay contact for the safe area load. The normal output state
    can be reversed using switches S1 and S2. Switch S3 is used
    to enable or disable line fault detection of the field circuit.
    During an error condition, the relays revert to their deenergized
    state and the LEDs indicate the fault according to
    NAMUR NE44.
    A unique collective error messaging feature is available when
    used with the Power Rail system.
    Features
    1 3
    4 6
    2
    5
    13 15
    12
    9
    10
    7
    14
    11
    8
    KFD2-SR2-Ex2.W
    1
    2
    OUT CHK PWR
    S2
    S1
    S3
    I II
    Front view
    LED yellow:
    Relay output Ι
    LED red:
    LB/SC channel Ι
    LED yellow:
    Relay output ΙΙ
    LED red:
    LB/SC channel ΙΙ
    Switch S3
    (LB/SC-monitoring)
    LED green:
    Power supply
    Removable terminals
    green
    Removable terminals
    blue
    Switch S1
    (Mode of operation channel Ι)
    Switch S2
    (Mode of operation channel ΙΙ)
    2
    Release date 2012-04-19 13:49 Date of issue 2012-04-19 132960_eng.xml
    Technical data KFD2-SR2-Ex2.W
    Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
    Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 2
    General specifications
    Signal type Digital Input
    Supply
    Connection Power Rail or terminals 14+, 15-
    Rated voltage 20 ... 30 V DC
    Ripple ≤ 10 %
    Rated current ≤ 50 mA
    Power loss 1 W
    Power consumption < 1.3 W
    Input
    Connection terminals 1+, 2+, 3-; 4+, 5+, 6-
    Rated values acc. to EN 60947-5-6 (NAMUR)
    Open circuit voltage/short-circuit current approx. 8 V DC / approx. 8 mA
    Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
    Line fault detection breakage I ≤ 0.1 mA , short-circuit I > 6 mA
    Pulse/Pause ratio ≥ 20 ms / ≥ 20 ms
    Output
    Connection output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
    Output I, II signal, relay
    Minimum switch current 2 mA / 24 V DC
    Energized/De-energized delay approx. 20 ms / approx. 20 ms
    Mechanical life 107 switching cycles
    Transfer characteristics
    Switching frequency ≤ 10 Hz
    Electrical isolation
    Output/power supply reinforced insulation according to IEC 61140, rated insulation voltage 300 Veff
    Output/Output reinforced insulation according to IEC 61140, rated insulation voltage 300 Veff
    Directive conbity
    Electromagnetic compatibility
    Directive 2004/108/EC EN 61326-1:2006
    Low voltage
    Directive 2006/95/EC EN 61010-1:2010
    Conbity
    Electromagnetic compatibility NE 21
    Protection degree IEC 60529
    Protection against electric shock IEC 61140
    Ambient conditions
    Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
    Mechanical specifications
    Protection degree IP20
    Mass approx. 150 g
    Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2
    Mounting on 35 mm DIN mounting rail acc. to DIN EN 60715
    Data for application in connection
    with Ex-areas
    EC-Type Examination Certificate PTB 00 ATEX 2080 , for additional certificates see www.pepperl-fuchs.com
    Group, category, type of protection ¬ II (1) G [Ex ia] IIC, II (1) D [Ex ia] IIIC
    Input [Ex ia] IIC, [Ex ia] IIIC
    Voltage Uo 10.5 V
    Current Io 13 mA
    Power Po 34 mW (linear characteristic)
    Supply
    Maximum safe voltage Um 253 V AC / 125 V DC (Attention! Um is no rated voltage.)
    Output
    Contact loading 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
    Maximum safe voltage Um 253 V AC (Attention! The rated voltage can be lower.)
    Statement of conbity Pepperl+Fuchs
    Group, category, type of protection ¬ II (3)G [Ex ic] IIC; [Ex nL] IIC
    Input [Ex ic] IIC; [Ex nL] IIC
    Voltage Uo 10.5 V
    Current Io 13 mA
    Power Po 34 mW (linear characteristic)
    Output
    Contact loading 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
    Release date 2012-04-19 13:49 Date of issue 2012-04-19 132960_eng.xml
    Technical data KFD2-SR2-Ex2.W
    Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
    Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 3
    Statement of conbity TÜV 99 ATEX 1493 X , observe statement of conbity
    Group, category, type of protection,
    temperature class
    ¬ II 3G Ex nA nC IIC T4
    Output
    Contact loading 50 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
    Electrical isolation
    Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
    Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
    Directive conbity
    Directive 94/9/EC EN 60079-0:2009, EN 60079-11:2007 , EN 60079-15:2005 , EN 61241-11:2006
    International approvals
    FM approval
    Control drawing 116-0035
    CSA approval
    Control drawing 116-0047
    IECEx approval IECEx PTB 11.0034
    Approved for [Ex ia] IIC , [Ex ia] IIIC , [Ex ia] I
    General inbation
    Supplementary inbation EC-Type Examination Certificate, Statement of Conbity, Declaration of Conbity, Attestation of
    Conbity and instructions have to be observed where applicable. For inbation see www.pepperlfuchs.
    com.
    Release date 2012-04-19 13:49 Date of issue 2012-04-19 132960_eng.xml
    Technical data KFD2-SR2-Ex2.W
    Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
    Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 4
    Power feed module KFD2-EB2
    The power feed module is used to supply the devices with 24 V DC via the Power Rail. The fuse-protected power feed module
    can supply up to 150 individual devices depending on the power consumption of the devices. A galvanically isolated mechanical
    contact uses the Power Rail to transmit collective error messages.
    Power Rail UPR-03
    The Power Rail UPR-03 is a complete unit consisting of the electrical inset and an aluminium profile rail 35 mm x 15 mm. To make
    electrical contact, the devices are simply engaged.
    Profile Rail K-DUCT with Power Rail
    The profile rail K-DUCT is an aluminum profile rail with Power Rail insert and two integral cable ducts for system and field cables.
    Due to this assembly no additional cable guides are necessary.
    Power Rail and Profile Rail must not be fed via the device terminals of the individual devices!
    Configuration
    7 8 9
    10 11 12
    1 2 3
    4 5 6
    13 14 15
    1
    2
    OUT CHK PWR
    S1
    S2
    S3
    1 2 3
    1 2 3
    S1
    S3
    II
    S2
    I
    Switch b
    Operating status
    Factory settings: switch 1, 2 and 3 in b I
    S Function Position
    1 Mode of operation
    Output I (relay)
    energized
    with high b current I
    with low b current II
    2 Mode of operation
    Output II (relay)
    energized
    with high b current I
    with low b current II
    3 Line fault detection ON I
    OFF II
    Control circuit Input signal
    Initiator high impedance/
    contact opened
    low b current
    Initiator low impedance/
    contact closed
    high b current
    Lead breakage,
    lead short-circuit
    Line fault
    Accessories
在线询盘/留言
  • 免责声明:以上所展示的信息由企业自行提供,内容的真实性、准确性和合法性由发布企业负责,本网对此不承担任何保证责任。我们原则 上建议您选择本网高级会员或VIP会员。
    0571-87774297