现货西门子6ES73211BL000AA0模块
数字量输入模板用来实现PLC与数字量过程信号的连接。使用于连接标准开关和两线制接近开关 (BERO)。
数字量输入模块具有下列机械特性:
具有8、16、32或64通道的模块。
希殿电气技术(上海)有限公司(西门子合作伙伴)
联系人 :康经理(销售工程师)
Q Q :192061030
手机 :18621061383(微信)
电话 :021-60541249
公司传真 :021-57271268
邮箱 :192061030@qq.com
数字量输入模块将来自过程的外部数字信号电平转换成控制器的内部信号电平(逻辑“0”或“1”)。
多种输入电压,可支持连接不同的控制信号:
除了经济性以及易于处理的特点外,该模块还具有其他特殊功能:
特殊模块还可处理过程工程,例如支持 NAMUR 标准。
Article number |
6ES7321-1BH02-0AA0 |
6ES7321-1BH50-0AA0 |
6ES7321-1BL00-0AA0 |
6ES7321-1BP00-0AA0 |
6ES7321-1BH10-0AA0 |
|
---|---|---|---|---|---|---|
SM321, 16DI, DC24V |
SM321, 16DI, DC24V, SOURCE INPUT |
SM321, 32DI, DC24V |
SM321, 64 DI, DC 24V, 3MS, SINK/SOURE |
SM321,16DI,DC24V, 0.05MS INPUT DELAY. |
||
Supply voltage |
|
|
|
|
|
|
Load voltage L+ |
|
|
|
|
|
|
|
24 V |
24 V |
24 V |
24 V |
24 V |
|
|
20.4 V |
20.4 V |
20.4 V |
20.4 V |
||
|
28.8 V |
28.8 V |
28.8 V |
28.8 V |
||
Input current |
|
|
|
|
|
|
from backplane bus 5 V DC, max. |
10 mA |
10 mA |
15 mA |
100 mA |
110 mA |
|
Power loss |
|
|
|
|
|
|
Power loss, typ. |
3.5 W |
3.5 W |
6.5 W |
7 W |
3.8 W |
|
Digital bs |
|
|
|
|
|
|
Number of digital bs |
16 |
16 |
32 |
64 |
16 |
|
Input characteristic curve in accordance with IEC 61131, type 1 |
Yes |
Yes |
Yes |
Yes |
Yes |
|
Number of simultaneously controllable bs |
|
|
|
|
|
|
all mounting bs |
|
|
|
|
|
|
|
64 |
|||||
|
32 |
|||||
horizontal installation |
|
|
|
|
|
|
|
16 |
16 |
32 |
64 |
16 |
|
|
16 |
16 |
16 |
32 |
16 |
|
vertical installation |
|
|
|
|
|
|
|
16 |
16 |
32 |
32 |
16 |
|
Input voltage |
|
|
|
|
|
|
|
DC |
DC |
DC |
DC |
DC |
|
|
24 V |
24 V |
24 V |
24 V |
24 V |
|
|
-30 to +5V |
-5 to +30V |
-30 to +5V |
-30 to +5V |
-30 to +5V |
|
|
13 to 30V |
-13 to -30V |
13 to 30V |
13 to 30V |
13 to 30V |
|
Input current |
|
|
|
|
|
|
|
7 mA |
7 mA |
7 mA |
4.2 mA |
7 mA |
|
Input delay (for rated value of b voltage) |
|
|
|
|
|
|
for standard bs |
|
|
|
|
|
|
|
No |
No |
No |
No |
No |
|
|
1.2 ms |
1.2 ms |
1.2 ms |
1.2 ms |
25 µs |
|
|
4.8 ms |
4.8 ms |
4.8 ms |
4.8 ms |
75 µs |
|
|
1.2 ms |
1.2 ms |
1.2 ms |
1.2 ms |
25 µs |
|
|
4.8 ms |
4.8 ms |
4.8 ms |
4.8 ms |
75 µs |
|
Cable length |
|
|
|
|
|
|
|
1 000 m |
1 000 m |
1 000 m |
1 000 m |
1 000 m |
|
|
600 m |
600 m |
600 m |
600 m |
600 m |
|
Encoder |
|
|
|
|
|
|
Connectable encoders |
|
|
|
|
|
|
|
Yes |
Yes |
Yes |
No |
Yes |
|
|
1.5 mA |
1.5 mA |
1.5 mA |
1.5 mA |
||
Isochronous mode |
|
|
|
|
|
|
Isochronous operation (application synchronized up to terminal) |
No |
No |
No |
No |
Yes |
|
Interrupts/diagnostics/status inbation |
|
|
|
|
|
|
Diagnostic functions |
No |
No |
No |
No |
No |
|
Alarms |
|
|
|
|
|
|
|
No |
No |
No |
No |
No |
|
|
No |
No |
No |
No |
No |
|
Diagnostic messages |
|
|
|
|
|
|
|
No |
|||||
Diagnostics indication LED |
|
|
|
|
|
|
|
No |
|||||
|
Yes |
Yes |
Yes |
Yes |
Yes |
|
Potential separation |
|
|
|
|
|
|
Potential separation digital bs |
|
|
|
|
|
|
|
No |
No |
No |
No |
No |
|
|
16 |
16 |
16 |
16 |
16 |
|
|
Yes; Optocoupler |
Yes; Optocoupler |
Yes; Optocoupler |
Yes; Optocoupler |
Yes; Optocoupler |
|
Isolation |
|
|
|
|
|
|
Isolation tested with |
500 V DC |
500 V DC |
500 V DC |
500 V DC |
500 V DC |
|
Connection b |
|
|
|
|
|
|
required front connector |
20-pin |
20-pin |
40-pin |
Cable: 6ES7392-4Bxx0-0AA0 terminal blocks: 6ES7392-1xN00-0AA0 |
20-pin |
|
Dimensions |
|
|
|
|
|
|
Width |
40 mm |
40 mm |
40 mm |
40 mm |
40 mm |
|
Height |
125 mm |
125 mm |
125 mm |
125 mm |
125 mm |
|
Depth |
120 mm |
120 mm |
120 mm |
112 mm |
120 mm |
|
Weights |
|
|
|
|
|
|
Weight, approx. |
200 g |
200 g |
260 g |
230 g |
200 g |
Article number |
6ES7321-7BH01-0AB0 |
6ES7321-1CH00-0AA0 |
6ES7321-1CH20-0AA0 |
6ES7321-1FH00-0AA0 |
|
---|---|---|---|---|---|
SM321, 16DI, 24V DC |
SM321, 16 DI, AC/DC 24-48V, 1CH/COMMON |
SM321, 16DI, DC48-125V |
SM321, 16 DI, 120/230V AC |
||
Supply voltage |
|
|
|
|
|
Load voltage L+ |
|
|
|
|
|
|
24 V |
24 V |
48 V |
||
|
20.4 V |
24 V |
48 V |
||
|
28.8 V |
48 V |
125 V |
||
Load voltage L1 |
|
|
|
|
|
|
24 V |
230 V; 120/230 V AC; all load voltages must have the same phase. |
|||
|
24 V |
||||
|
48 V |
||||
Input current |
|
|
|
|
|
from load voltage L+ (without load), max. |
90 mA |
||||
from backplane bus 5 V DC, max. |
130 mA |
100 mA |
40 mA |
29 mA |
|
Power loss |
|
|
|
|
|
Power loss, typ. |
4 W |
1.5 W; at 24 V; 2,8 W at 48 V |
4.3 W |
4.9 W |
|
Digital bs |
|
|
|
|
|
Number of digital bs |
16 |
16 |
16 |
16 |
|
Input characteristic curve in accordance with IEC 61131, type 1 |
Yes |
Yes |
Yes |
||
Input characteristic curve in accordance with IEC 61131, type 2 |
Yes |
||||
horizontal installation |
|
|
|
|
|
|
16 |
16 |
8 |
16 |
|
|
16 |
16 |
8; 6 to Ue 146 V |
16 |
|
vertical installation |
|
|
|
|
|
|
16 |
16 |
8 |
16 |
|
Input voltage |
|
|
|
|
|
|
DC |
AC/DC |
DC |
AC |
|
|
24 V |
24 V; DC 24 or 48 V |
48 V; 48 V DC to 125 V DC |
||
|
24 V; 24 V AC or 48 V AC (0 ... 63 Hz) |
230 V; 120/230 V AC (47 ... 63 Hz) |
|||
|
-30 to +5V |
-5V AC to +5V AC |
-146 V DC to +15 V DC |
0 to 40V |
|
|
13 to 30V |
14V AC to 60V AC |
30 V DC to 146 V DC |
79 to 264V |
|
Input current |
|
|
|
|
|
|
7 mA |
2.7 mA |
3.5 mA |
6.5 mA; (120V, 60Hz), 16mA (230V, 50Hz) |
|
Input delay (for rated value of b voltage) |
|
|
|
|
|
for standard bs |
|
|
|
|
|
|
Yes; 0.1 / 0.5 / 3 / 15 / 20 ms |
No |
No |
No |
|
|
16 ms |
0.1 ms |
25 ms |
||
|
16 ms |
3.5 ms |
25 ms |
||
|
0.7 ms |
||||
|
16 ms |
3 ms |
25 ms |
||
Cable length |
|
|
|
|
|
|
1 000 m |
1 000 m |
1 000 m |
1 000 m |
|
|
600 m |
600 m |
600 m |
600 m |
|
Encoder |
|
|
|
|
|
Connectable encoders |
|
|
|
|
|
|
Yes |
Yes |
Yes |
Yes |
|
|
2 mA |
1 mA |
1 mA |
2 mA |
|
Isochronous mode |
|
|
|
|
|
Isochronous operation (application synchronized up to terminal) |
Yes |
No |
No |
No |
|
Interrupts/diagnostics/status inbation |
|
|
|
|
|
Diagnostic functions |
Yes; Parameterizable |
No |
No |
No |
|
Alarms |
|
|
|
|
|
|
Yes; Parameterizable |
No |
No |
No |
|
|
Yes; Parameterizable |
No |
No |
No |
|
Diagnostic messages |
|
|
|
|
|
|
Yes; to I< 1 mA |
||||
Diagnostics indication LED |
|
|
|
|
|
|
Yes |
No |
No |
No |
|
|
Yes |
Yes |
Yes |
Yes |
|
Potential separation |
|
|
|
|
|
Potential separation digital bs |
|
|
|
|
|
|
No |
Yes |
No |
No |
|
|
16 |
1 |
8 |
4 |
|
|
Yes; Optocoupler |
Yes; Optocoupler |
Yes; Optocoupler |
Yes; Optocoupler |
|
Permissible potential difference |
|
|
|
|
|
between different circuits |
170 V DC/120 V AC |
146 V DC/132 V AC |
|||
Isolation |
|
|
|
|
|
Isolation tested with |
500 V DC |
1500 V AC |
1500 V DC |
4 000 V DC |
|
Connection b |
|
|
|
|
|
required front connector |
20-pin |
40-pin |
20-pin |
20-pin |
|
Dimensions |
|
|
|
|
|
Width |
40 mm |
40 mm |
40 mm |
40 mm |
|
Height |
125 mm |
125 mm |
125 mm |
125 mm |
|
Depth |
120 mm |
120 mm |
120 mm |
120 mm |
|
Weights |
|
|
|
|
|
Weight, approx. |
200 g |
260 g |
200 g |
240 g |
Article number |
6ES7321-1EL00-0AA0 |
6ES7321-1FF01-0AA0 |
6ES7321-1FF10-0AA0 |
|
---|---|---|---|---|
SM321, 32DI, AC120V |
SM321, 8DI, AC120/230V |
SM321, 8 DI, AC/DC 120/230V, 1CH/COMMON |
||
Load voltage L1 |
|
|
|
|
|
120 V |
230 V; 120/230V AC |
230 V; 120/230 V AC; all load voltages must have the same phase. |
|
Input current |
|
|
|
|
from backplane bus 5 V DC, max. |
16 mA |
29 mA |
100 mA |
|
Power loss |
|
|
|
|
Power loss, typ. |
4 W |
4.9 W |
4.9 W |
|
Digital bs |
|
|
|
|
Number of digital bs |
32 |
8 |
8 |
|
Input characteristic curve in accordance with IEC 61131, type 1 |
Yes |
Yes |
||
Input characteristic curve in accordance with IEC 61131, type 2 |
Yes |
|||
horizontal installation |
|
|
|
|
|
32 |
|||
|
24 |
8 |
8 |
|
vertical installation |
|
|
|
|
|
32 |
8 |
8 |
|
Input voltage |
|
|
|
|
|
AC |
AC |
AC |
|
|
120 V; 47 ... 63 Hz |
230 V; 120/230 V AC (47 ... 63 Hz) |
120 V; 120/230 V AC (47 ... 63 Hz) |
|
|
0 to 20V |
0 to 40V |
0 to 40V |
|
|
74 to 132V |
79 to 264V |
79 to 264V |
|
Input current |
|
|
|
|
|
21 mA |
6.5 mA; (120 V); 11 mA (230 V) |
7.5 mA; (120 V); 17.3 mA (230 V) |
|
Input delay (for rated value of b voltage) |
|
|
|
|
for standard bs |
|
|
|
|
|
No |
No |
No |
|
|
15 ms |
25 ms |
25 ms |
|
|
25 ms |
25 ms |
25 ms |
|
Cable length |
|
|
|
|
|
1 000 m |
1 000 m |
1 000 m |
|
|
600 m |
600 m |
600 m |
|
Encoder |
|
|
|
|
Connectable encoders |
|
|
|
|
|
Yes |
Yes |
Yes |
|
|
4 mA |
2 mA |
2 mA |
|
Isochronous mode |
|
|
|
|
Isochronous operation (application synchronized up to terminal) |
No |
No |
No |
|
Interrupts/diagnostics/status inbation |
|
|
|
|
Diagnostic functions |
No |
No |
No |
|
Alarms |
|
|
|
|
|
No |
No |
No |
|
|
No |
No |
No |
|
Diagnostics indication LED |
|
|
|
|
|
No |
No |
No |
|
|
Yes; per channel |
Yes |
Yes |
|
Potential separation |
|
|
|
|
Potential separation digital bs |
|
|
|
|
|
No |
No |
Yes |
|
|
8 |
2 |
1 |
|
|
Yes; Optocoupler |
Yes; Optocoupler |
Yes; Optocoupler |
|
Isolation |
|
|
|
|
Isolation tested with |
2500 V DC |
4 000 V DC |
1500 V AC |
|
Connection b |
|
|
|
|
required front connector |
40-pin |
20-pin |
40-pin |
|
Dimensions |
|
|
|
|
Width |
40 mm |
40 mm |
40 mm |
|
Height |
125 mm |
125 mm |
125 mm |
|
Depth |
120 mm |
120 mm |
120 mm |
|
Weights |
|
|
|
|
Weight, approx. |
300 g |
240 g |
240 g |