*** Spare part *** SIMATIC ET 200MP. PROFINET IO device Interface module IM 155-5 PN ST for ET 200MP electronic modules; up to 12 IO modules without PS; up to 30 IO modules with additional PS; integrated 2-port switch; RJ45 shared device; MRP; IRT >=0.25 ms; isochronous mode Firmware update; I&M0...3; FSU with 500 ms
|
General inbation
|
Product type designation
|
IM 155-5 PN ST
|
HW functional status
|
FS01
|
Firmware version
|
V3.0.0
|
Vendor identification (VendorID)
|
0x002A
|
Device identifier (DeviceID)
|
0X0312
|
Product function
|
● I&M data
|
Yes; I&M0 to I&M3
|
Engineering with
|
● STEP 7 TIA Portal configurable/integrated as of version
|
V13 / V13
|
● STEP 7 configurable/integrated as of version
|
V5.5 SP3 / -
|
● PROFINET as of GSD version/GSD revision
|
V2.3 / -
|
Configuration control
|
via user data
|
No
|
via dataset
|
Yes
|
Supply voltage
|
Rated value (DC)
|
24 V
|
permissible range, lower limit (DC)
|
20.4 V
|
permissible range, upper limit (DC)
|
28.8 V
|
Reverse polarity protection
|
Yes
|
Short-circuit protection
|
Yes
|
Mains buffering
|
● Mains/voltage failure stored energy time
|
5 ms
|
Input current
|
Current consumption (rated value)
|
0.2 A
|
Current consumption, max.
|
1.2 A
|
Inrush current, max.
|
9 A
|
I²t
|
0.09 A²·s
|
Power
|
Infeed power to the backplane bus
|
14 W
|
Power available from the backplane bus
|
2.3 W
|
Power loss
|
Power loss, typ.
|
4.5 W
|
Address area
|
Address space per module
|
● Address space per module, max.
|
256 byte; per b / output
|
Address space per station
|
● Address space per station, max.
|
512 byte; per b / output
|
Hardware configuration
|
Integrated power supply
|
Yes
|
System power supply can be plugged in to left of IM
|
Yes
|
Number of permissible power segments
|
3
|
Rack
|
● Modules per rack, max.
|
30; I/O modules
|
Interfaces
|
Number of PROFINET interfaces
|
1
|
1. Interface
|
Interface types
|
● Number of ports
|
2
|
● integrated switch
|
Yes
|
● RJ 45 (Ethernet)
|
Yes
|
Protocols
|
● PROFINET IO Device
|
Yes
|
● Media redundancy
|
Yes; PROFINET MRP
|
Interface types
|
RJ 45 (Ethernet)
|
● Transmission procedure
|
PROFINET with 100 Mbit/s full duplex (100BASE-TX)
|
● 100 Mbps
|
Yes
|
● Autonegotiation
|
Yes
|
● Autocrossing
|
Yes
|
Protocols
|
PROFINET IO Device
|
Services
|
— Isochronous mode
|
Yes
|
— IRT
|
Yes
|
— PROFIenergy
|
No
|
— Prioritized startup
|
Yes
|
— Shared device
|
Yes
|
— Number of IO Controllers with shared device, max.
|
2
|
Redundancy mode
|
● MRP
|
Yes
|
● MRPD
|
No
|
● PROFINET system redundancy (S2)
|
No
|
Open IE communication
|
● TCP/IP
|
Yes
|
● SNMP
|
Yes
|
● LLDP
|
Yes
|
Isochronous mode
|
Isochronous operation (application synchronized up to terminal)
|
Yes
|
Equidistance
|
Yes
|
shortest clock pulse
|
250 µs
|
max. cycle
|
4 ms
|
Interrupts/diagnostics/status inbation
|
Status indicator
|
Yes
|
Alarms
|
Yes
|
Diagnostics function
|
Yes
|
Diagnostics indication LED
|
● RUN LED
|
Yes; Green LED
|
● ERROR LED
|
Yes; Red LED
|
● MAINT LED
|
Yes; yellow LED
|
● Connection display LINK TX/RX
|
Yes; yellow LED
|
Potential separation
|
between backplane bus and electronics
|
No
|
between PROFINET and all other circuits
|
Yes
|
between supply and all other circuits
|
No
|
Isolation
|
Isolation tested with
|
707 V DC (type test)
|
Ambient conditions
|
Ambient temperature during operation
|
● horizontal installation, min.
|
0 °C
|
● horizontal installation, max.
|
60 °C
|
● vertical installation, min.
|
0 °C
|
● vertical installation, max.
|
40 °C
|
Connection b
|
ET-Connection
|
● via BU/BA Send
|
No
|
Dimensions
|
Width
|
35 mm
|
Height
|
147 mm
|
Depth
|
129 mm
|
Weights
|
Weight, approx.
|
310 g
|